IN_PROD_538
»
Temperature Control Equipment
IN_PROD_539
»
Thermo-Chillers (Circulating Fluid Temperature Controllers)
Thermo-chiller/Standard Type HRS100/150
・No heater is required, as the circulating fluid is heated using only
the heat exhausted by the refrigerating circuit. ・Compatible with power supplies in Europe, Asia, Oceania, North, Central, and South America ・Low-noise design: 70 dB (A) ・Outdoor installation: IPX4 ・Compact, Space saving |
|
Other Data |
---|
Series | Flow characteristics 4/2→3/5(A/B→E) C[dm3/(s・bar)] |
Flow characteristics 4/2→3/5(A/B→E) b |
Applicable cylinder size |
Power consumption (W) |
Model |
---|---|---|---|---|---|
HRS100 HRS150 |
5 to 35℃ | 9.5 kW 14.5 kW (60 Hz) |
±1.0℃ | Air-cooled refrigeration/ Water-cooled refrigeration |
Tap water Deionized water Ethylene glycol aqueous solution (15%) |
Thermo-chiller/Standard TypeHRS100/150
Series | Download |
---|---|
HRS100 HRS150 |
|
■Circulating fluid can be heated without a heater.
Heating method using discharged heat makes a heater unnecessary.
Heating-up time: 1/10
■Cooling capacity: 10 kW/15 kW
■Set temperature range: 5° C to 35° C
■Max. ambient temperature: 45° C
■Temperature stability: ±1.0° C
■Low-noise design: 70 dB(A)
■Electric conductivity control set
(Optional accessories)
(With DI filter + Solenoid valve kit for control)
(Optional accessories)
(With DI filter + Solenoid valve kit for control)
The electric conductivity of the circulating fluid can be set with the controller monitor arbitrarily.
Set control range: 5.0 to 45.0 μ S/cm
■Relief valve set
(Optional accessories)
(Optional accessories)
Prevents increase in circulating fluid discharge pressure.
(Relief pressure: 0.32 MPa
■Power supply (24 VDC) available
Power can be supplied from the terminal block of the thermo-chiller to external switches etc.
■Communication function
The serial communication (RS232C/RS485) and contact I/Os (2 inputs and 3 outputs) are equipped as standard. Communication with the user’s equipment and system construction are possible, depending on the application. A 24 VDC output can be also provided, and is available for a flow switch (SMC’s PF3W, etc.).